0.6/1 kV - unarmoured single core fire resistance cables
Applied standards: IEC 60502-1, IEC 60331

NOMINAL CROSS SECTION AREA
|
|
INSULATION THICKNESS
|
SHEATH THICKNESS
|
APPROX. OVERALL DIAMETER
|
CONDUCTOR RESISTANCE AT 20°C
|
PACKING LENGTH
|
|
|
(mm2)
|
|
|
(mm)
|
(mm)
|
(mm)
|
(Ω/km)
|
(m)
|
1 x 1.5
|
|
|
0.7
|
1.4
|
6
|
12.1
|
500/c
|
1 x 2.5
|
|
|
0.7
|
1.4
|
6.5
|
7.41
|
500/c
|
1 x 4
|
|
|
0.7
|
1.4
|
7
|
4.61
|
500/c
|
1 x 6
|
|
|
0.7
|
1.4
|
7.5
|
3.08
|
500/c
|
1 x 10
|
|
|
0.7
|
1.4
|
8.5
|
1.83
|
1500
|
1 x 16
|
|
|
0.7
|
1.4
|
9.5
|
1.15
|
1500
|
1 x 25
|
|
|
0.9
|
1.4
|
11
|
0.727
|
1000
|
1 x 35
|
|
|
0.9
|
1.4
|
13
|
0.524
|
1000
|
1 x 50
|
|
|
1.0
|
1.4
|
14
|
0.387
|
1000
|
1 x 70
|
|
|
1.1
|
1.4
|
16
|
0.268
|
1000
|
1 x 95
|
|
|
1.1
|
1.5
|
18
|
0.193
|
1000
|
1 x 120
|
|
|
1.2
|
1.5
|
20
|
0.153
|
1000
|
1 x 150
|
|
|
1.4
|
1.6
|
22
|
0.124
|
1000
|
1 x 185
|
|
|
1.6
|
1.6
|
24
|
0.0991
|
1000
|
1 x 240
|
|
|
1.7
|
1.7
|
27
|
0.0754
|
500
|
1 x 300
|
|
|
1.8
|
1.8
|
30
|
0.0601
|
500
|
1 x 400
|
|
|
2.0
|
1.9
|
34
|
0.0470
|
500
|
1 x 500
|
|
|
2.2
|
2.0
|
38
|
0.366
|
500
|
|
|
|
|
|
|
|
|
|