Slide 1 Slide 4 Slide 3

Electrical products

Mechanical products

ATATA INSULATION

M&E Contractors

Support online

Sale & CEO

Tel: +84 913 554 030

Vị trí

Our partners

PVC insulated 3 cores flexible wires

Applied standards: TCVN 6610-5 (IEC 60227-5)

 

NO. OF CORE X NOMINAL CROSS SECTION AREA

 

INSULATION THICKNESS 

SHEATH THICKNESS

APPROX. OVERALL DIMENSION

CONDUCTOR RESISTANCE AT 20°C

PACKING LENGTH

   

(mm2)

   

(mm) 

(mm)

(mm)

(Ω/km)

(m)

3 x 0.5 (*)

   

0.6

0.8

6.5

39.0

500/c

3 x 0.75

   

0.6

0.8

7

26.0

500/c

3 x 1

   

0.6

0.8

7.5

19.5

500/c

3 x 1.25 (*)

   

0.7

0.8

8

15.6

300/c

3 x 1.5

   

0.7

0.8

8.5

13.3

300/c

3 x 2 (*)

   

0.8

1.0

9.5

9.79

300/c

3 x 2.5

   

0.8

1.0

10

7.98

300/c

3 x 3 (*)

   

0.8

1.0

11

6.59

300/c

3 x 4 (**)

   

1.0

1.8

14

4.95

1000

3 x 6 (**)

   

1.0

1.8

15

3.30

1000

3 x 10 (**)

   

1.0

1.8

19

1.91

1000

3 x 16 (**)

   

1.0

1.8

21

1.21

1000

3 x 25 (**)

   

1.2

1.8

25

0.780

1000

                      

   

                   

                  

                   

                  

                 


(*) The products are applied base standard, which is built on reference to IEC 60227-5, JIS C 3306.
(**) The products are applied base standard, which is built on reference to IEC 60502-1 Std. with rate voltage 0.6/1 kV
In addition to the product categories above , we will produce all kinds of specifications products according to customer requirements