Slide 1 Slide 4 Slide 3

Electrical products

Mechanical products

ATATA INSULATION

M&E Contractors

Support online

Sale & CEO

Tel: +84 913 554 030

Vị trí

Our partners

0.6/1 kV unarmoured single core cables - Cu/XLPE/PVC

Applied standards: IEC 5935, (IEC 60502-1)

 

NOMINAL CROSS SECTION AREA

 

INSULATION THICKNESS

SHEATH THICKNESS

APPROX. OVERALL DIAMETER

CONDUCTOR RESISTANCE AT 20°C

PACKING LENGTH

   

(mm2)

   

(mm)

(mm)

(mm)

(Ω/km)

(m)

1x1.5

   

0.7

1.4

6

12.1

200/c

1x2.5

   

0.7

1.4

6.5

7.41

200/c

1x3.5(*)

   

0.7

1.4

7

5.20

200/c

1x4

   

0.7

1.4

7

4.61

200/c

1x5.5(*)

   

0.7

1.4

7.5

3.33

200/c

1x6

   

0.7

1.4

7.5

3.08

200/c

1x8(*)

   

0.7

1.4

8

2.31

2000

1x10

   

0.7

1.4

8.5

1.83

2000

1x14(*)

   

0.7

1.4

9

1.30

2000

1x16

   

0.7

1.4

9.5

1.15

2000

1x22(*)

   

0.9

1.4

11

0.832

2000

1x25

   

0.9

1.4

11

0.727

1000

1x35

   

0.9

1.4

12

0.524

1000

1x38(*)

   

0.9

1.4

13

0.492

1000

1x50

   

1.0

1.4

14

0.387

1000

1x60(*)

   

1.0

1.4

15

0.307

1000

1x70

   

1.1

1.4

16

0.268

1000

1x95

   

1.1

1.5

18

0.193

1000

1x100(*)

   

1.1

1.5

19

0.182

1000

1x120

   

1.2

1.5

20

0.153

1000

1x125(*)

   

1.2

1.5

20

0.147

1000

1x150

   

1.4

1.6

22

0.124

500

1x185

   

1.6

1.6

24

0.0991

500

1x240

   

1.7

1.7

28

0.0754

500

1x300

   

1.8

1.8

30

0.0601

500

1x400

   

2.0

1.9

34

0.0470

500

1x500

   

2.2

2.0

38

0.0366

500

(*) The products are applied base standard, which is built on reference to IEC 60502-1, JIS C 3605 Std.

In addition to the product categories above , we will produce all kinds of specifications products according to customer requirements